Over Head Power Transmission Purposes.
Reference: | IS-398 (Part-2) :1996 |
---|---|
Conductor: | Conductor Containing Aluminum & Galvanized Steel Wire Built in Concentric Layer, Material Conforming to IS:5484:1978 |
Resistivity of Material: | 0.028264 Ohm mm2/m at 20°C |
Transmission Lines: | Widely used in overhead transmission lines for high-voltage power distribution. |
---|---|
Rural Electrification: | Suitable for extending electricity to remote areas. |
High Strength-to-Weight Ratio: | ACSR provides the mechanical strength necessary for long spans and high tension while remaining lightweight. |
---|---|
Corrosion Resistance: | Galvanized steel reinforcement protects against rust and environmental damage. |
Cost Efficiency: | Offers an economical solution for power transmission without compromising performance. |
Flexibility: | Suitable for various applications, making it a versatile choice for electrical engineers. |
Size in SQ MM | No. of wire/Steel Wire size |
No. of Wire/AL. Wire Size |
Breaking Load in KN |
Resistance at 20°C in Ohm/Km |
---|---|---|---|---|
10 | 1/1.5 | 6/1.5 | 3.97 | 2.7800 |
18 | 1/1.96 | 6/1.96 | 6.74 | 1.6180 |
20 | 1/2.11 | 6/2.11 | 7.61 | 1.3940 |
30 | 1/2.59 | 6/2.59 | 11.12 | 0.9289 |
50 | 1/3.35 | 6/3.35 | 18.25 | 0.5524 |
80 | 1/4.09 | 6/4.09 | 26.91 | 0.3712 |
100 | 7/1.57 | 6/4.72 | 32.41 | 0.2792 |